| Product characteristics |
| Magnetic-inductive flow meter |
| Connector |
| Process connection: G2 flat seal |
| connection to pipe by means of an adapter |
| Function programmable |
| Totaliser function |
| Empty pipe detection |
2 outputs
OUT1 = flow monitoring (binary), flow rate meter (pulse), preset meter (binary)
OUT2 = flow monitoring or temperature monitoring (analogue or binary) |
| Input for counter reset |
| 4-digit alphanumeric display |
| Measuring range |
| 5…600 l/min |
| Application |
| Application | | Conductive liquids
(conductivity:>= 20 µS/cm / viscosity: < 70 mm²/s at 40 °C) |
| Pressure rating [bar] | | 16 |
| Medium temperature [°C] | | -10…70 |
| Electrical data |
| Electrical design | | DC PNP/NPN |
| Operating voltage [V] | | 18…32 DC ¹) |
| Current consumption [mA] | | < 150 |
| Insulation resistance [MΩ] | | > 100 (500 V DC) |
| Protection class | | III |
| Reverse polarity protection | | yes |
| Outputs |
| Output function | | OUT1: normally open / normally closed programmable or pulse or frequency or empty pipe detection or IO-Link
OUT2: normally open / normally closed programmable or analogue (4…20 mA; 0…10 V, scalable) or empty pipe detection |
| Current rating [mA] | | 2 x 250 |
| Voltage drop [V] | | < 2 |
| Short-circuit protection | | pulsed |
| Overload protection | | yes |
| Analogue output | | 4…20 mA; 0…10 V |
| Max. load [Ω] | | 500 (4…20 mA) |
| Min. load [Ω] | | 2000 (0…10 V) |
| Pulse output | | flow rate meter |
| Frequency range [Hz] | | 0.1…10000 |
| Measuring / setting range |
| Empty pipe detection | | normally closed / open |
| Flow monitoring |
| Measuring range | | 5…600 l/min | 0.3…36 m³/h |
| Display range | | -720…720 l/min | -43.2…43.2 m³/h |
| Resolution | | 0.5 l/min | 0.02 m³/h |
| Set point, SP | | 8…600 l/min | 0.5…36 m³/h |
| Reset point, rP | | 5…597 l/min | 0.3…35.8 m³/h |
| Analogue start point, ASP | | 0…480 l/min | 0…28.8 m³/h |
| Analogue end point, AEP | | 120…600 l/min | 7.2…36 m³/h |
| Flow end point, FEP | | 20…600 l/min; 1.2…36 m³/h |
| Low flow cut-off, LFC | | 5…15 l/min | 0.3…0.9 m³/h |
| in steps of | | 0.5 l/min | 0.02 m³/h |
| Frequency end point, FrEP | | 0.01…10 kHz |
| in steps of | | 10 Hz |
| Measuring dynamics | | 1:120 |
| Volumetric flow quantity monitoring |
| Measuring range [l…m³] | | 0.0…9999 x 10³ |
| Display range [l…m³] | | 0.0…9999 x 10³ |
| Set point, SP [l…m³] | | 0.0…9999 x 10³ |
| Pulse value | | 0.1 l…600 x 10³ m³ |
| in steps of | | 0.1 l |
| Pulse length [s] | | 0.008…2 |
| Temperature monitoring |
| Measuring range [°C] | | -20…80 |
| Display range [°C] | | -40…100 |
| Resolution [°C] | | 0.2 |
| Set point, SP [°C] | | -19.2…80.0 |
| Reset point, rP [°C] | | -19.6…79.6 |
| Analogue start point, ASP [°C] | | -20…60 |
| Analogue end point, AEP [°C] | | 0…80 |
| in steps of [°C] | | 0.2 |
| Accuracy / deviations |
| Flow monitoring |
| Accuracy | | ± (0.8% MW + 0.5% MEW) ²) |
| Repeatability | | ± 0.2% MEW |
| Pressure loss (dP) / flow rate (Q) | |  |
| Temperature monitoring |
| Accuracy [K] | | ± 1 (bei 25 °C, Q > 15 l/min) |
| Temperature drift | | ± 0.0333 °C / K |
| Reaction times |
| Power-on delay time [s] | | 5 |
| Flow monitoring |
| Start-up delay [s] | | 0…50 |
| Response time [s] | | < 0.35 (dAP = 0) |
| Damping, dAP [s] | | 0…5 |
| Temperature monitoring |
| Response time [s] | | T09 = 3 (Q > 15 l/min) |
| Software / programming |
| Programming options | | Hysteresis / window; NO / NC; output logic; current / voltage / frequency / pulse output; start-up delay; display can be deactivated; display unit; empty pipe detection |
| Interfaces |
| IO-Link Device |
| Transfer type | | COM2 (38.4 kBaud) |
| IO-Link revision | | 1.1 |
| SDCI standard | | IEC 61131-9 CDV |
| IO-Link Device ID | | 389d / 00 01 85h |
| Profiles | | Smart Sensor: Process Data Variable; Device Identification |
| SIO mode | | yes |
| Required master port type | | A |
| Process data analogue | | 3 |
| Process data binary | | 2 |
| Min. process cycle time [ms] | | 5 |
| Environment |
| Ambient temperature [°C] | | -10…60 |
| Storage temperature [°C] | | -25…80 |
| Protection | | IP 65 / IP 67 |
| Tests / approvals |
| Pressure equipment directive | | Article 3, section 3 – sound engineering practice |
| EMC | | | DIN EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD | | DIN EN 61000-4-3 HF radiated: | 10 V/m | | DIN EN 61000-4-4 Burst: | 2 kV | | DIN EN 61000-4-5 Surge: | 1 kV | | DIN EN 61000-4-6 HF conducted: | 10 V |
|
| Shock resistance | | | DIN EN 60068-2-27 | 20 g (11 ms) |
|
| Vibration resistance | | | DIN EN 60068-2-6 | 5 g (10…2000 Hz) |
|
| MTTF [Years] | | 78 |
| Mechanical data |
| Process connection | | G2 flat seal |
| Materials (wetted parts) | | stainless steel 316L / 1.4404; stainless steel 316Ti / 1.4571; PEEK (polyether ether ketone); Hastelloy C-4 (2.4610); Centellen; FKM |
| Housing materials | | stainless steel 316L / 1.4404; stainless steel 316Ti / 1.4571; PEI; FKM; PBT-GF 20; elastolan |
| Weight [kg] | | 3.071 |
| Displays / operating elements |
| Display | | | Display unit | 6 x LED green (l/min, m³/h, l, m³, 10³, °C) | | Switching status | 2 x LED yellow | | Measured values | 4-digit alphanumeric display | | Programming | 4-digit alphanumeric display |
|
| Electrical connection |
| Connection | | M12 connector; Gold-plated contacts |
Wiring| Core colours | | BK | black | | BN | brown | | BU | blue | | WH | white |
|  |  | | Colours to DIN EN 60947-5-6 | | ———————— | | OUT1: 6 options: | | switching output empty pipe detection | | switching output flow rate monitoring | | frequency output flow rate monitoring | | pulse output quantity meter | | signal output preset counter | | IO-Link | | OUT2: 6 options: | | switching output empty pipe detection | | switching output flow rate monitoring | | switching output temperature monitoring | | analogue output flow rate | | analogue output temperature | | Input for counter reset |
|
|
|
| Accessories |
| Accessories (included) | | 2 x packing washer (Centellen); Label |
| Remarks |
| Remarks | | | ¹) to DIN EN 50178, SELV, PELV | | ²) Q > 15l/min, medium and ambient temperature +22 °C ± 4 K | | MW = measured value | | MEW = final value of the measuring range |
|
| Pack quantity [piece] | | 1 |
| ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen — We reserve the right to make technical alterations without prior notice. — GB — SM2000 — 12.11.2014 |